Product Structure
Conductor: Single or stranded bare copper or tinned copper wire complying with IEC 60228 VDE 02955 class standard.
Insulation: PVC/TI1 complying with DIN VDE O281 Part 1 + HD21.1.
Color Code: The cores are identified by colors according to HD402 standard.
Standards Applied: HD 21.3 S3, VDE-0281 Part-3, CE Low Voltage Directive, 73/23/EEC, and 93/68/EEC.
Technical Parameters
Rated Voltage: 300V/500V
Test Voltage: 2500V complying with DIN VDE O281 Part 2 + HD21.2.
Minimum Bending Radius Fixed Installation: 12.5XD (cable outer diameter).
Mobile Installation: 12.5xD (cable outer diameter).
Temperature Range Fixed Installation: -30°C to +80°C; Mobile Installation: -5°C to +70°C.
Flame Retardant: Complies with EC60332-1-2 + EN60332-1-2, UL VW-1 + CSA FT1, IEC 60332.1.
Insulation Resistance: 10 Ma x km.
Characteristics and Compliance
Characteristics: Solid-core single-core wire, easy to strip, cut, and install, complying with EU harmonized standards.
Certifications: ROHS CE.
Typical Applications
Used for flexible connections inside electrical appliances, instruments, and electrical devices. Suitable for connections between instruments, devices, distribution panels, power distributors (boards), and telecommunication equipment. Also applicable for grounding wires in protective systems and alarm lights.